Page 76
Tables
Parameter list
In the parameter list all necessary settings for correct operation of the UMG96S, such as CT data or
device address, are mentioned. The values in the parameter list can be written and read. Date and
time in address 700 are an exception and can be written only. On address 410 of the measured
value list, date and time can be read in seconds since 1.1.1970.
Measured value list
The measured value list contains the measured and calculated measured values, condition data of
the inputs and outputs as well as the protocolled values for reading out.
Formats
CHAR
= 1 Byte
INT
= 2 Byte; (high before low Byte)
LONG
= 4 Byte; (high before low Byte)
STRING1
= 32 Byte; Byte 1 = row 1, Bit1=1.meas. value table, Bit2=2.meas. value table ...
Byte 2 =row 2, Bit1=1. meas. value table, Bit2=2.meas.value table ...
STRING2
= 6 Byte; Hour, minute, second, day, month, year
FDATA
= 2 Byte; Data set number
4 Byte; Time since 1.1.1970
10 Byte; Data string
1 Byte; Profile number
1 Byte; Error information
Representation of CosPhi within UMG96S
Measured value indication
measured value list and data memory
Analog outputs and switching outputs
capacitive
inductive
1,00
0,00cap
0,00ind
-100
-1
+100
+0
-100 +100
0 0
1,00 1,00
Attention!
Only the PC software GridVis can use the maximum setting range of some parameters. At
UMG96S, values can be entered up to 999999.
m
Attention!
For some parameters, only software GridVis can use the full setting range. At UMG96S, only
values up to 999999 can be set.
m
m
The measured values (current, voltage, power etc.) in the measured value lists do not contain
transformer ratios.