Page 27
Fault
Phase shift ind/kap.
Programming data
are lost.
Real power too small
/ too big.
Real power cons./
supply exchanged.
An output does not
react.
"
EEE
" in Display
The device does not
work properly de-
spite the above.
Possible reason
Current path assigned to the
wrong voltage path.
The device was exposed to
higher electromagnetical inter-
ference than indicated in the
technical data.
CT ratio badly programmed.
Current path assigned to
wrong voltage path.
At least one CT connection
exchanged.
Current path assigned to the
wrong voltage path.
Output badly programmed.
Output badly connected.
See error messages.
Device defective.
Remedy
Check and correct connection.
Improve external protection measures
like shielding, filtering, earth or local
separation.
Read and program CT ratio.
Check and correct connection.
Check and correct connection.
Check and correct connection.
Check and correct programming.
Check and correct connection.
Please send the device to the manufac-
turer with a detailed description of the er-
ror.