Page 79
Addr. Description
Setting range
Type
Unit Presettin.
600
Current transformer, primary
6)
1 .. 10000
INT
A
5
601
Current transformer, secondary
6)
1 .. 5
INT
A
5
602
Voltage transformer, primary
6)
100 .. 60000
INT
V
400
4)
603
Voltage transformer, secondary
6)
100 .. 400
INT
V
400
4)
604
Indication profile, actual
5)
STRING1
-
-
605
Indication rotation profile, actual
5)
STRING1
-
-
700
Date and time
5)
STRING2
-
-
701
Option clock, yes=1, no= 0
read only
CHAR
-
-
702
Ring buffer, Data set number, address
read only
INT
-
-
703
Option Ringpuffer, ja=1, nein= 0
read only
CHAR
-
-
800
Write in EEPROM
0 .. 4
CHAR
-
0
Bit 1 = 1, Write calibration data.
Bit 2 = 1, Write programming data.
Bit 4 = 1, Write counter.
Bit 8 = 1, Write min./max. values.
911
Serial number
read only
LONG
-
######
913
Software Release
read only
INT
-
###
914
Hardware Expansion
read only
INT
-
###
Parameter list Part 3
1)
0 = OR, 1 = AND
2)
0 = not inverted, 1 = inverted
3)
0 = 5Sec., 1 = 10Sec., 2 = 30Sec., 3 = 60Sec., 4 = 300Sec., 5 = 480Sec., 6 = 900Sec.
4)
In 300V standard version: 400V; In 150V special version: 100V.
5)
These values can only be read and written with GridVis.
6)
The parameters for current and voltage transformer ratios can be read at UMG96S only.
Attention!
For some parameters, only software GridVis can use the full setting range. At UMG96S, only
values up to 999999 can be set.