Page 47
Software Release (Addr. 913)
The internal software of the UMG96S is im-
proved and expanded continuously. The soft-
ware release of the device is given by a 3 digit
number. The software release cannot be
changed by the user.
Hardware expansion (Addr. 914)
The available options of the UMG96S can be
called up under the address 914. For each avail-
able option, a Bit is set. The result is a binary
value, that is indicated in decimal form by the
UMG96S.
Example 1
The UMG96S indicates the decimal value 96
under address 914.
Option
Hex
Binary
Description
0x01
0000 0001
Memory (EEPROM)
0x02
0000 0010
Clock
0x04
0000 0100
Analog outputs 1/2
0x08
0000 1000
Digital output or
pulse output 1/2
0x10
0001 0000
Digital input 1/2
0x20
0010 0000
Profibus
0x40
0100 0000
RS232
0x80
1000 0000
RS485
Option Profibus
Option RS232
96
= 0x60 = 0110 0000
Example 2
The UMG96S displays the decimal value 248
under address 914.
Digital output 1/2
Digital input 1/2
Profibus
RS232
RS485
248
= 0xf8 = 1111 1000
Address =914
Value=
96
L1
L2
L3
Содержание UMG 96S