UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
www.janitza.de
22
NOTE
The option "supply voltage of 24 V" is only valid for
the UMG 96-PA (see section
7.1 Nominal voltages
7.1.1
Three-phase four-conductor network
with grounded neutral conductor
Networks and nominal voltages suitable for your
device:
Maximum nominal voltage of the
network according to UL
U
L-N /
U
L-L
66V / 115V
120V / 208V
127V / 220V
220V / 380V
230V / 400V
240V / 415V
260V / 440V
277V / 480V
347V / 600V
400V / 690V
417V / 720V
Maximum nominal voltage of
the network
Fig.
Nominal network voltages suitable for measuring
inputs acc. to EN 60664-1:2003
Fig.
Example, schematic diagram (
UMG 96-PA
) -
Measurement in three-phase 4-conductor
systems.
DC
AC/DC
PE
347V/600V 50/60Hz
L2
L3
N
L1
Auxiliary supply
Voltage measurement
4M
4M
4M
4M
V1
V3
V2
V
N
UMG 96-PA
N
L1
240 V
50/60Hz
Ground-
ing of the
system
7.2 Disconnect switch
Install a suitable circuit breaker for the supply volt-
age in the building installation in order to discon-
nect the device from voltage and current.
·Install the circuit breaker near the device and
within reach of the user.
·Mark the circuit breaker as the isolation device
for this piece of equipment.
7.3 Supply voltage
Operation of the device requires a supply voltage.
The type and level of the supply voltage for your
device can be found on the rating plate. Also note:
·Before applying the supply voltage, ensure that
the voltage and frequency match the specifica-
tions on the rating plate.
·Connect the supply voltage via a UL/IEC ap-
proved fuse to the plug-in terminals on the rear of
the device.
·After connecting the supply voltage, the display
appears. If no display appears, check whether
the supply voltage is within the nominal voltage
range.
NOTE
·The device optionally allows the connection of
100 V voltage transformers!
·
The following applies for the UMG 96-PA-
MID / MID+ when measuring voltage using
voltage transformers: Use calibrated/permis-
sible voltage transformers for MID-compliant
measurement (secondary: 3 x 57.7/100 V -
3 x 230/400 V)!
Maximum nominal voltage of the
network according to
MID (UMG 96-PA-MID/MID+)