UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
www.janitza.de
40
To determine the mains frequency, the device
requires a voltage of >20 V
eff
(4-conductor mea-
surement) or an L1-L2 voltage of >34 V
eff
(3-con-
ductor measurement) at voltage measuring input
V1.
NOTE
Devices with the setting
Auto
take about 5 sec-
onds to determine the mains frequency. During
this time, the measured values
do not
maintain
the guaranteed measurement uncertainty.
NOTE
If the mains frequency is outside the range of 45-
65 Hz:
·There is no error or warning alert.
·When a constant frequency (
50/60 Hz
) is indi-
cated, the corresponding setting is used.
·When automatic frequency detection is select-
ed (
Auto
), the last determined frequency in the
range of 45-65 Hz is used.
The determination of the frequency runs over a
period of 10 seconds. The frequency does
not
represent a 200 ms measured value!
Fig.
Measurement window with the item Nominal
frequency activated.
·Open the
Configuration
window as previously
described.
·Use buttons 3 (
) and 4 (
) to select the item
Measurement
and confirm with button 6 (
Enter
).
·The
Measurement
window appears with the
entries:
- Transformer.
- Nominal current.
- Nominal frequency.
·Use buttons 3 (
) and 4 (
) to select the item
12.4.2 Nominal current
For a defined operation of the device, you need
the nominal current in addition to the settings of
the current and voltage transformer ratios.
·Open the
Configuration
window as previously
described.
·Use buttons 3 (
) and 4 (
) to select the item
Measurement
and confirm with button 6 (
Enter
).
·The
Measurement
window appears.
·Use buttons 3 (
) and 4 (
) to select the item
Nominal current
and confirm with button 6
(
Enter
).
Fig.
Measurement window with the item Nominal
current activated.
·The item for the
Nominal current
is shown "yel-
low".
·Use buttons 2 (
) and 5 (
) to change the
position of the digit to be set for each item and
use buttons 3 (
) and 4 (
) to change the digit
(-1/+1).
·Confirm your entries with button 6 (
Enter
) or end
the action by pressing button 1 (
Esc
).
NOTE
The
UMG 96-PA-MID/MID+
supports automatic
frequency determination only (45-65 Hz)!
Nominal frequency
and confirm with button 6
(
Enter
).
·The item for the
Nominal frequency
is shown
"yellow".
·Select your frequency range with buttons 3 (
)
and 4 (
).
·Confirm your entries with button 6 (
Enter
) or end
the action by pressing button 1 (
Esc
).
·To return to the measuring display
Home
, press
button 1 twice (
Esc
) and then press button 2
(
Home
).
Setting ranges for
Nominal frequency
:
·
Auto
(45-65 Hz)
-
Standard setting
·
60 Hz
(const. frequency)
·
50 Hz