UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
www.janitza.de
74
After a battery replacement, the device adopts the
time (date) set by the user after
90 seconds
. This
allows the user to correct incorrect entries within
the 90 s. Otherwise, the device adopts the time
(date) immediately.
You configure the time (date) once with password
entry
·on the device display;
·in the GridVis
®
software.
NOTE
Confirming the message displayed above
("Change time") deletes all stored data re-
cords of the meter reading cycle on the
device!
For the meter reading cycle function of the
UMG 96-PA-MID+ please observe:
Configure the time (date, time) as described in
section „12.6 System“ on page 43.
If the time change amounts to more than
31 days
the following warning appears on the device
display:
Fig.
Warning of data records being deleted
14.6 UMG 96-PA-MID+ -
Meter reading cycle display
After setting the time on the
UMG 96-PA-MID+
,
you can access the meter reading display of the
device as follows:
·If you are
not
in the measuring display
Home
,
you can go to this view by pressing button 2
(
Home
).
·Open the menu with button 1 (
Menu
).
·Use buttons 3 (
) and 4 (
) to select the menu
item
Energy & MID
and confirm with button 6
(
Enter
).
·A submenu appears with the item
Meter reading
cycle
.
·Use buttons 3 (
) and 4 (
) to select the menu
item
Meter reading cycle
and confirm with but-
ton 6 (
Enter
).
·The
Meter reading cycle
window appears with
the entries:
- Status.
- Meter reading (of delivered and applied energy
in kWh).
- Date and time (15 min display).
Fig.
Meter reading cycle window with valid data records