NOTE
·Measured values and Modbus addresses for
the analog outputs can be configured easily
and clearly in the GridVis
®
software (see www.
janitza.de).
·Using the GridVis
®
software requires a connec-
tion between the measurement device and a
PC (server) running the GridVis
®
software (see
section „8. Connection and PC connections“
·Also observe the documentation for the RCM
modules.
Example for the measured value
Active power
:
·In the
Configuration
window, select the item
Modbus editor
and confirm with button 6 (
Enter
).
·The
Communication
/
Modbus Editor
window
appears with the items
Address
and
Value
.
·Select the item
Address
and press button 6
(
Enter
).
·The item
Address
is shown "yellow".
·Use buttons 2 (
), 5 (
), 3 (
) and 4 (
) to
configure the number
30001
.
·Confirm the entry with button 6 (
Enter
).
·Then select the item
Value
and press button 6
(
Enter
).
·The item
Value
is shown "yellow".
·Use buttons 2 (
), 5 (
), 3 (
) and 4 (
) to
configure the number
19026
for the measured
value
Active power sum, L1-L3
.
·Then configure the
Start
and
End value
of the
active power in the addresses
30002
and
30004
.
For example, start value 500 W and end value
1000 W. Please note that the measured value
variables must always be entered in the basic
unit (e.g. W, A, V).
Further information on this example can be found in