13.15.3 Synchronization priority
An external synchronization takes place according
to different priorities:
·
Priority 1: Modbus synchronization
For this, set the "Enable flag" (addr.: 822) using
the Modbus tool or select the "Synchronization
via Modbus" option in the GridVis
®
software in
the drag indicator configuration area.
·
Priority 2: Synchronization via
digital input 3
For this, set the Modbus parameter "FUNC_
SYNC_RECORD" (addr. 30048) to the value 4,
or select the option "Drag indicator synchroniza-
tion" in the GridVis
®
software in the peripherals
(digital input 3) configuration area.
Note: Do
NOT
select the option "Synchronization
via Modbus" in the drag indicator configuration!
·Priority 3: Internal synchronization
Modbus
address
Function
Configura-
tion
range
820
Set trigger flag for
drag indicator synchronization
0 .. 1
821
Time base in seconds
60 .. 65535
822
Enable flag of the
Modbus trigger
0 .. 1
823
Capture time in seconds
0 .. 255
30048
Configuration of the inputs
0 .. 4*
Fig.
Table of Modbus addresses for a synchronization
* 0 = FUNC_NONE;
1 = FUNC_TARIFF;
2 = FUNC_SYNC_CLOCK_MIN;
3 = FUNC_SYNC_CLOCK_H;
4 = FUNC_SYNC_RECORD
Fig.
Configuration "Synchronization via
digital input 3 in the GridVis
®
software
Fig.
Drag indicator configuration in the GridVis
®