17. Service and maintenance
Prior to outbound delivery, the device is subjected
to various safety tests and is marked with a seal.
If a device is opened, the safety tests must be re-
peated. A warranty is only assumed for unopened
devices.
17.1 Repair and calibration
Repair and calibration of the device must only be
carried out by the manufacturer or an accredited
laboratory! The manufacturer recommends cali-
brating the device every 5 years!
The calibration validity period of the
UMG 96-PA
MID
depends on applicable national law
WARNING
Warning of unauthorized tampering or improp-
er use of the device.
Opening, dismantling or unauthorized manip-
ulation of the device which goes beyond the
mechanical, electrical or other operating limits
indicated can lead to material damage or injury, up
to and including death.
·
Only electrically qualified personnel are
permitted to work on the devices and their
components, assemblies, systems and cur-
rent circuits!
·
Always use your device or component only
in the manner described in the associated
documentation.
·
In the event of visible damage, or for the
purpose of repair and calibration, return the
device to the manufacturer!
17.2 Front panel foil and display
Please note the following for the care and clean-
ing of the front foil and the display:
NOTE
Material damage due to improper care and
cleaning of the device.
The use of water or other solvents, such as dena-
tured alcohol, acids, acidic agents for cleaning the
front cover or display can damage or destroy the
device. Water can, for example, penetrate into the
device housing and destroy the device.
·
Clean the device, the front foil or the display
with a soft cloth.
·
Use a cloth moistened with clear water for
heavy soiling.
·
Clean the front foil and the display,
·
e.g. of fingerprints, with a special LCD clean-
er and a lint-free cloth.
·
Do not use acids or acidic agents to clean
the devices.
17.3 Service
For questions not answered or described in this
manual, please contact the manufacturer. Please
be certain to have the following information ready
to answer any questions:
·Device designation (see rating plate)
·Serial number (see rating plate)
·Software release (see system display)
·Measured voltage and supply voltage
·An exact error description.
17.4 Device adjustment
The manufacturer adjusts the devices before
delivery. No readjustment is required when the
environmental conditions are complied with.
17.5 Firmware update
For a firmware update, connect your device to
a computer and obtain access via the
GridVis
®
software:
·Open the Firmware Update Wizard by clicking
on "Update Device" in the “Extras" menu.
·Select your update file and perform the update.
Fig.
Updating the device firmware in the GridVis
®
software
NOTE
No firmware update is possible for the
UMG 96-PA-MID/MID+
!