UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
13.16 Recordings
Two recording profiles are preconfigured in the
factory default setting of the device. Adaptation
and expansion of recordings can be done using
the GridVis
®
software.
·The smallest time base for recordings is 1 min-
ute.
·A maximum of 4 recordings with 29 measured
values each is possible. If min and max values
are defined as well, the number is reduced to 19
or 14 values.
·Within the recording configuration, measured
values are defined via a time base according to
the types
Average value
,
Sample, Maximum or
Minimum
.
·
Average value
type: Arithmetic mean value of
the measured values over a defined period of
time.
·
Maximum
and
Minimum
types: Maximum or
minimum values of a specified time period.
·
Sample
type: Measured value at the end of
the defined time period.
Note
: Work values are only recorded with the type
Sample
.
Recording 1
The following measured values are recorded with
a time base of 15 minutes:
·Effective voltage L1
·Effective voltage L2
·Effective voltage L3
·Effective current L1
·Effective current L2
·Effective current L3
·Effective current, sum L1..L3
·Active power L1
·Active power L2
·Active power L3
·Active power, sum L1..L3
·Apparent power L1
·Apparent power L2
·Apparent power L3
·Apparent power, sum L1..L3
·cos phi(math.) L1
·cos phi(math.) L2
·cos phi(math.) L3
·cos phi(math.) Sum L1..L3
·Reactive power fundamental oscillation L1
·Reactive power fundamental oscillation L2
·Reactive power fundamental oscillation L3
·Reactive power fundamental oscillation sum L1..
L3
Recording 2
The following measured values are recorded with
a time base of 1 hour:
·Applied active energy L1
·Applied active energy L2
·Applied active energy L3
·Applied active energy, sum L1..L3
·Inductive reactive energy L1
·Inductive reactive energy L2
·Inductive reactive energy L3
·Inductive reactive energy, sum L1..L3
Fig.
Recording configuration in the GridVis
®
software