UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
14.5 Battery replacement and time setting on
the UMG 96-PA-MID and UMG 96-PA-
MID
+
NOTE
The device:
·
Saves correct data records only if the time is
set!
·
Sets the time to 01-01-2000 and is therefore
considered "not set” when the supply voltage
is disconnected and at the same time the
battery is spent or after a battery replace-
ment.
To ensure that a battery replacement is carried
out without loss of data, the device provides an
advance warning with the alarm
"Battery capaci-
ty below 10%!":
Figures: Device alarm "Battery capacity below 10%"
After a battery replacement, an alarm appears on
the device display stating
"Please set time"
.
UMG 96-PA-MID+
UMG 96-PA-MID+
NOTE
If the alarm "Battery capacity below 10%" ap-
pears on the device display, replace the battery
Figures: Device alarm "Please set time”
Configure the time (date, time) as described in
section „12.6 System“ on page 43.
WARNING
Risk of injury due to electrical voltage!
Severe bodily injury or death can result from:
·Touching bare or stripped leads that are ener-
gized.
·Device inputs that pose a hazard when
touched.
Observe the following when handling your
device and when changing the battery,
before
starting work:
·
Disconnect the system/device from the
power supply!
·
Secure it against being switched on!
·
Check to be sure it is de-energized!
·
Ground and short circuit!
·
Cover or block off adjacent live parts!