Positioning module IMD20, IMD40
Notes on safe and EMC-compliant installation
•
Unshielded signal and control lines should not be used. If t
least be twisted.
heir use is inevitable they should at
•
Even shielded cables will inevitably have short unshielded ends (unless shielded connector
e following applies:
corresponding pins of the connectors; Maximum length 40
- Connect the total shield on the motor side plane to the connector housing or motor housing;
um length 40 mm.
housings are used). In general, th
- Connect the inner shields to the
mm.
- Length of the unshielded cores 35 mm maximum.
- Connect the total shield on the controller side plane to the PE terminal; Maximum length 40
mm.
Maxim
DANGER!
For safety reasons, all PE ground conductors must be connected prior to initial
operation.
The EN 50178 regulations for protective earthing must be complied with during
installation!
17