Positioning module IMD20, IMD40
CanOpen protocol
This object can be used to r
1 on the sub-index 1 starts
ealise the offset adjustment of the internal A/D converter. The writing of a
the automatic adjustment. For this, the module has to be in the "Switched
On" (or "Operation Enable") state.
Under the sub-indices 2 and 3, the current offset values can be queried. These are given in units of
32 times the internal A/D converter resolution (11 bit, -1023 ... +1023). It is also possible to directly
write the offset values.
Actual motor current
Index Sub Name
Typ
Attrib Map Defaultwert Bedeutung
2070
Actual Motor Current RECORD
Actual motor current
(internal unit)
2070
00
Number of Entries
Unsigned 8
CONST
N
2
Number of entries
2070
01
Iq
Signed 16
RO
N
0
Actual current Iq
2070
02
Id
Signed 16
RO
N
0
Actual current Id
2070
03
Iu
Signed 16
RO
N
0
Actual current Iu
2070
04
Iv
Signed 16
RO
N
0
Actual current Iv
2070
05
lw
Signed 16
RO
N
0
Actual current lw
Actual analogue target value
Index Sub Name
Type
Attrib Map Default
value
Meaning
2071 00 Actual analogue
input
Signed 16
RO
Y
0
Actual analogue target
value -1023 ... +1023.
DC Bus Voltage
Index Sub Name
Typ
Attrib Map Defaultwert Bedeutung
2072
00
Number of Entries
Unsigned 8
CONST
N
2
2072 01 IMD20 Actual Active
Level Status
Unsigned 8
RO
N
0
At IMD20: 1= DC Bus
Voltage over 30V, 0 = DC
Bus Voltage under 30V
2072 02 IMD40 Actual
Voltage
Unsigned 16
RO
N
0
At IMD40: actual DC Bus
Voltage
The following objects are used to start and configure the test signals.
Current control test signal
Index Sub Name
Typ
Attrib Map Defaultwert Bedeutung
2090
Test-Input for
Encoder and Current
Control
RECORD
Test signal for encoder
and current controller
2090
00
Number of Entries
Unsigned 8
CONST
N
3
Number of entries
2090
01
Test-Input Duration
Unsigned 8
RW
N
25
Duration of test signal
2090
02
Iq-Test-Input Value
Unsigned 16
RW
N
100
Amplitude of the test
signal for the current Iq
2090
03
Id-Test-Input Value
Unsigned 16
RW
N
100
Amplitude of the test
signal for the current Id