Ver. 3.604 (31/03/05)
p43
INNER RANGE IQ. PLUS Programmer’s Manual.
PULSE COUNTING
1) Enable Pulse Count operation for any Zone Inputs that are to be used as “Pulse Count Zones”.
Enable Option 4 - “Pulse Count” in the Zone Options.
NEXT 651 (Zone 1) to 666 (Zone 16)
2) Program the Pulse Count Value (0 to 15. Factory Default = 2).
NEXT 901
3) Program the Pulse Time (0 to 255 Seconds. Factory Default = 60) .
NEXT 902
4) If an Alarm on any Pulse Count Zone is to increment the Count on all Pulse Count Zones;
Enable Option 4 - “Pulse Count Handover” in “General Options 3”.
NEXT 892
SECURITEL REPORTING FORMAT
1) Select Option 3 - “Securitel” as the Port 0 Communications Task.
(or Port 1)
NEXT 515 (517)
2) When this Communications task is selected using a Terminal, the baud rate (516 for Port 0 or 518 for Port 1)
NEXT 516 (518)
is also Set to 1200 (Option 1); CID and Dual Reporting are disabled
and the Securitel Report Format is set (Option 4 only) is seleted(505).
NEXT 505
(when used with Upload / DownLoad all options must be set Manually)
Note: Securitel is a reporting communications task, using some of the functions of PSTN reporting
and is selected in the communications tasks options. The options allow for Securitel OR Contact ID reporting.
However Domestic reporting can be used with Securitel, the Dual reporting option is NOT required in this case.
3) Program the Hard ID into the General Area / Area 1 Client Code in DECIMAL.
The Hard ID is provided by the Central Monitoring Station.
NEXT 521
Note: Before connecting the STU to the IQ PANEL the hard ID must be programmed,
The PANEL or the STU must be restarted if the Hard ID value is changed.
4) Securitel does not use a phone connection, the Securitel “STU” is connected to the IQ “Port 0” or “Port 1”
via an Inner Range cable PN: 995524
Options that are selected to report to the “Dialer” will report via Securitel
NEXT 506
NEXT 899