INNER RANGE IQ. PLUS Programmer’s Manual.
17
Hand-over Force Arm. Same as Type 2 - “Handover” except that Users will always be allowed to arm an Area assigned to this Zone type
when the Zone is unsealed. i.e. The “Force Arming” function will always apply regardless of the setting in General Options 1, Option 3 -
Force Arming. (Address 890. Default is “Not Enabled”)
Allows for Handover Zones that may need to be unsealed when arming. e.g. A PIR that detects movement near the Terminal.
18
Final Exit.(Do Not use as a normal Zone) Final Exit button using a normally closed contact, when contact opens, the zone will go
into Alarm, which terminates any exit delay.
ZONE OPTIONS
Programming Addresses for Zone Options programming:
1 - Silent
2 - Siren Lockout
3 - Dialer Lockout
4 - Pulse Count
5 - Self-Test Zone
6 - Day Alarm Zone
7 - Normally Open (Change Sense)
8 - Spare
Zone Options allows various processing options to be selected for each individual Zone.
1
Silent.
When this option is selected, the Zone will not trigger the siren. If “Silent” and “Siren Lockout” options are both set then the
Zone will behave according to the Silent option.
2
Siren Lockout.
This option allows the Zone to trigger the Siren only for the number of times specified in “Swinger Shutdown Siren
Count” (Address 913) during one arming cycle. If “Silent” and “Siren Lockout” options are set then the Zone will behave according to the
Silent option.
3
Dialer Lockout.
This option allows a Zone to trigger the Dialer only for the number of times specified in “Swinger Shutdown Dialer
Count” (Address 914) during one arming cycle.
If “Single-Hit” reporting is required, select this option and set the Swinger Shutdown Dialer Count to a value of “1”.
If full Multi-break reporting is required, this option must not be selected.
617-650
651-666
Spare
(Option Data)
1 - No
2 - Yes *
3 - Yes
4 - No
5 - No
6 - No
7 - No
8 - No
* Zones 1 to 8 only.
ADDRESS
DEFAULT
FUNCTION
(Data Type)
Zone
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Address
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
SEALED
ALARM (Contact
open)
IQ ARMED
Final Exit
Button
EXIT DELAY