p26
Ver. 3.604 (31/03/05)
INNER RANGE IQ. PLUS Programmer’s Manual.
14A. ASSIGN AREA 1 TO ALL ZONES USED.
NEXT 701 to 716
DEFAULT: Area 1 assigned to Zones 1 to 8.
Assign Area 1 to all the Zones that are used in the system by enabling
Option 1 (Area 1) in the relevant Addresses from 701 to 716.
13.
PROGRAM THE MULTI-AREA GENERAL OPTIONS.
NEXT 891
14B. ASSIGN THE REQUIRED AREA/S TO ZONES.
NEXT 701 to 716
DEFAULT: Area 1 assigned to Zones 1 to 8.
Assign the required Area/s to all the Zones that are used in the system by
enabling the Options in the relevant Addresses from 701 to 716.
NOTE: Normally, only one Area is assigned to a Zone.
1 - Area 1 assigned.
3 - Area 3 assigned.
2 - Area 2 assigned.
4 - Area 4 assigned.
Is the system a Multi-Area system?
Single Area System.
NO
YES. Multi Area System.
Go to Step 14a.
Option
Default
Description
1
Multi Area system.
No
4
All Areas Siren Off control.
No
Any User with Disarm
privileges can cancel Siren.
Zone
1
2
3
4
5
6
7
8
Address
701
702
703
704
705
706
707
708
Zone
9
10
11
12
13
14
15
16
Address
709
710
711
712
713
714
715
716
t
t
t
How to Enter Data.
Select Address: Key in the Installer PIN Code; Press
then enter the 3 digit Address
(A1 to A3 Lamps will flash to prompt for each digit). The current Data will be displayed.
Enter Data:
Enter the new Data
.. (1-16 digits) OR Option/s to Select/De-select
, then
. NOTE:
clears the current field of all data or settings ready for new data.
Zone
1
2
3
4
5
6
7
8
Address
701
702
703
704
705
706
707
708
Zone
9
10
11
12
13
14
15
16
Address
709
710
711
712
713
714
715
716