p22
Ver. 3.604 (31/03/05)
INNER RANGE IQ. PLUS Programmer’s Manual.
2.
SELECT THE END-OF-LINE RESISTOR TYPE.
NEXT 600
DEFAULT: Option 3 - 3k3 Single End-of-Line.
END-OF-LINE RESISTOR TYPES:
Single EOL:
0
-1k
1
-1k5
2
-2k2
3
-3k3
4
-3k9
5
-4k7
6
-5k6
7
-6k8
8
-10k
9
-12k
10
-22k
Dual EOL:
11
-2k2, 2k2
12
-2k2, 6k8
13
-3k3, 6k8
14
-10k, 10k (Provides Tamper state. 1st Value is Series Resistor, 2nd Value is Resistor across contacts)
Zone Doubed:
15
-1k, 3k3, 6k8 Zone doubled
16
-1k, 3k3, 6k8 Zone doubled (no seperate tamper state)
See installation manual for details.
1.
DEFAULT THE SYSTEM.
a)
Logon to the Terminal using the Installer PIN code and select DEFAULTING THE CONTROL MODULE.
NEXT 098
-Enter PIN, <NEXT>, 0, 9, 8.
b)
Select the Default Option.
! CAUTION: This option completely erases all current programming.
- n, <ENTER>.
0:
Completely resets the database to Factory Default settings, including the Installer Code and Master Code.
Where “n” is the Default option.
1, 2 or 3:
Completely resets the database to one of the Installer Presets, including the Installer Code and Master Code.
See page 16 “Defaulting the system” and the “Factory Defaults” Table on page 85 for details.
c)
Reset the Control Module.
Disconnect the AC Supply input and the Battery from the Control Module. Wait 5 seconds, then Re-connect power.
3.
PROGRAM THE ZONE TYPE/S.
NEXT 601 to 616
DEFAULT: Zone 1; Type 1-Delayed.
Zone 2; Type 2-Handover
Zones 3 to 16; Type 0-Instant.
Program the new Zone Type for Zones that are not “Instant” Zones.
Zone Types:
t
t
t
0
Instant
1
Delayed
2
Handover
3
Away Instant / Home Isolate
4
Away Instant / HomeDelay
5
Away Delay / Home Isolate
6
Away Delay / Home Delay
7
Away Delay / Home Instant
8
Away Handover / Home Isolate
9
Away Handover / Home Delay
10
24 Hour Burglary
11
24 Hour Fire
12
24 Hour Panic
13
24 Hour duress
14
KeySwitch Arm
15
KeySwitch Home
16
Delay / Force Arm
17
Handover / Force Arm
Zone
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Address
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616