INNER RANGE IQ. PLUS Programmer’s Manual.
ZONE AREAS
Zones must be assigned to an Area before they can be processed by the system.
If the system is configured for “Single Area mode”, then all the Zones that are used, must be assigned to the General Area / Area 1.
(Single Area / Multi-Area mode is selected in General Options 2; Address 891, Option 1. Default is Single Area mode)
If the system is configured for “Multi-Area mode”, then each Zone is assigned to one or more Areas, depending on the system
requirements.
Any Zone not assigned to any Area is considered as an unused Zone.
Programming Addresses for Zone Area programming:
This data sets the Area/s that the Zone will be assigned to.
Zones are normally only assigned to one Area.
A separate Address is used for each Zone Input as per the table above.
TIMEZONES
TimeZones can be programmed to define a Start time and End time, and the Days of the Week on which the TimeZone will be valid.
TimeZone programming also provides a “Holiday” option to be enabled when assigning the Days, to allow the TimeZone to still be valid on
any dates defined as Holidays.
Once programmed, TimeZones can be used to arm & disarm Areas &/or control Auxiliary outputs automatically.
TIMEZONE 1 PROGRAMMING.
TIMEZONE 2 PROGRAMMING.
TIMEZONE 3 PROGRAMMING.
TIMEZONE 4 PROGRAMMING.
Each TimeZone has 5 Address locations for defining:
Start Hr
Start Min
End HrEnd Min
Valid Days of the Week
701-716
717-749
750-754
755-759
760-764
765-769
(Option Data)
Zones 1 to 8
1 - Area 1
Zones 9 to 16
No Areas assigned.
Spare
9am-5pm Mon to Fri
9am-1pm Sat & Sun
7am-8pm All days
8pm-7am All days
ADDRESS
DEFAULT
FUNCTION
(Data Type)
Zone
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Address
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
NOTE:
The time zone value, when changed, will not take effect until after
the following midnight.