Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
System description
Hardware description
>
5.1.3
Monitoring concept
22919
The controller monitors the supply voltage for overvoltage and undervoltage.
In case of undervoltage, the controller switches off.
>
Monitoring and securing mechanisms
22941
>
Switch off outputs via solid-state switch
23273
WARNING
Danger due to unintentional deactivation of all outputs!
If monitoring routines detect a system error:
>
The device switches off the energy for all outputs of the affected output groups.
→ chapter
Output groups
→ chapter
List of outputs
(
During the program process, the output switches are under the user's full software control. For further
safety, the corresponding applicable national regulations must be complied with.
If an error occurs during the program sequence, it is possible to disconnect the output switches from
voltage via the FB
OutputGroup
in order to separate critical plant sections.
11575
WARNING
Danger due to unintentional and dangerous start of machine or plant sections!
► When creating the program, the programmer must ensure that no unintentional and dangerous
start of machines or plant sections after a fault (e.g. e-stop) and the following fault elimination
can occur!
Realise restart inhibit.
► In case of an error, set the outputs concerned to FALSE in the program!