System configuration
Configure interfaces
>
7.3
Configure interfaces
23100
>
7.3.1
Configure serial interface
23151
The CODESYS service communication via RS232 only works with the preset baud rate.
For other purposes, the device supports the following baud rates:
9 600 baud
19 200 baud
28 800 baud
38 400 baud
57 600 baud
115 200 baud (preset)
Setting the interface:
→
Interface configuration file comconf.cfg
(
>
7.3.2
Configure Ethernet interface
23152
Setting the interface:
→
Interface configuration file comconf.cfg
(
Factory setting:
IP address = 192.168.82.247
Subnet mask = 255.255.255.0
Gateway address = 192.168.82.21
UDP port = 12345
23450
NOTICE
Only use the Ethernet interface in a secure network environment (e.g. separate network or VPN)!
Otherwise, unauthorised persons can read or manipulate data or tamper with the functions of the
device.
>
The the IP parameter of the Ethernet interface
23455
In order to update the runtime system of the CR711S via a network, the device must be connected to
the corresponding network. For the configuration of the Ethernet interface, the following options are
available:
Manual
The user defines the parameters of the Ethernet interface manually:
IP address,
Subnet mask,
gateway address
► Observe the
Address assignment in Ethernet networks
(
) in
Ethernet networks!
Automatic
The interface parameters are set via the Dynamic Host Configuration
Protocol (DHCP).
(the development of this function is still in progress)
Setting the interface:
→
Interface configuration file comconf.cfg
(