Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
Installation
Carry out installation
► Use the [0] key to call up the menu item [Continue update process].
>
Order number, software and hardware version are read from the device.
If an update is possible using the read data:
>
The [ecomatController Update Menu] appears.
>
Otherwise: Error message and return to the [ecomatController Update Start Menu].
► Follow the instructions on the screen.
>
The updated process is executed.
ATTENTION
► After loading the first file
cmd.ifm
and after the instruction on the screen, execute a power-on
reset of the controller.
>
Otherwise the controller may be destroyed!
► After the power-on reset, continue the update process following the instructions on the screen.
>
The user is informed about the success of the update process.
If the update process is finished successfully:
► Disconnect the voltage supply.
► Re-connect the voltage supply after the waiting time.
>
The PLC boots with a new operating system.