Status LEDs
>
9.3.2
Status LED: system PLC (SYS0, SYS1)
23436
The SYS0 LED is for the "standard PLC".
The SYS1 LED is for the "safety PLC".
The status of one of the PLCs has no influence on the display of the other PLC.
LED colour
Display
Description
Green
permanently on
RUNTIME_OPERATING
no application loaded
Green
Flashing with 2 Hz
RUNTIME_OPERATING
Application = RUN
(time frame = 200 ms)
Yellow
Flashing with 2 Hz
RUNTIME_DEBUG_RUN
Application = RUN
(time frame = 200 ms)
Yellow
permanently on
RUNTIME_DEBUG_STOP
Application = STOP
Red
flashes with 10 Hz
RUNTIME_STOP
Error class = B
(time frame = 200 ms)
>
9.3.3
Status LED: System bootloader (SYS0)
23426
The SYS0 LED is for the bootloader status only.
The SYS1 LED is switched off in these cases.
23561
Only execute the bootloader update when explicitly requested by ifm!
LED colour
Display
Description
Green
Flashing with 5 Hz
no runtime system loaded
(time frame = 200 ms)
green-yellow
flashes with 5 Hz
Bootloader update process active
(time frame = 200 ms)