Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
System description
Hardware description
>
Output type OUT Supply-A
23125
The output
OUT3000
is used to supply sensors with a stable voltage (5 V or 10 V) that is not affected
by fluctuations of the supply voltage.
13402
NOTICE
Reference voltage output can get damaged!
► Do NOT apply any external voltage!
Setting and measurement via FB
or via system configuration:
>
Setting / measurement via system configuration
22942
Setting the reference voltage:
► In the device tree, select [Local_IO] > [Outputs] > tab [Parameter] > [OUT3000]
► Activate the required list element in the column [Value]:
for 5 V: [
OUT_SENSOR_05
] or
for 10 V: [
OUT_SENSOR_10
]
Monitoring of the values at the reference voltage output:
► In the device tree, select [Local_IO] > [Outputs] > tab [IO-Mapping] > [OUT3000_I]
>
[OutVoltageDiag] indicates the measured voltage in [mV]
[OutCurrentDiag] indicates the measured voltage in [mA]
>
Setting /measurement via FB Output
23422
Setting the reference voltage:
► Use the inputs in the FB output as follows:
[uiChannel] = 3000
[eMode] = [
OUT_SENSOR_05
] (for 5 V) or
[eMode] = [
OUT_SENSOR_10
] (for 10 V)
Monitoring of the values at the reference voltage output:
► Read the outputs in the FB output as follows:
>
[uiOutVoltage] indicates the measured voltage in [mV]
[uiOutCurrent] indicates the measured current in [mA]
Details
→ FB