39
ifm
Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
System description
Hardware description
>
Input type IN MULTIFUNCTION-A
23081
Binary and analogue inputs
Block diagram
IN MULTIFUNCTION-A
IN#### =
Connection of multi-function input no. ####
(CR) = device
(1) = input filter
(2) = analogue current measurement
R
E
= 300
(3) = binary input, plus-switching
R
E
= 10 k
(4) = analogue voltage measurement
0...10 V / 0...32 V
(5) = measured value
(6) = reference voltage for ratio
Configure input
→ Chapter System configuration
Possible operating modes:
Binary input CSI (B
L
) (R
E
= 10 k
) or Namur
Analogue current measurement 0...20 mA
Analogue voltage measurement 0...10 V
Analogue voltage measurement 0...32 V
Analogue voltage measurement, ratiometric to the reference voltage
>
Input type IN FREQUENCY-A/B
23083
Binary and fast inputs
Block diagram
IN FREQUENCY-A/B
IN#### =
Connection of frequency / counting input
no. ####
(CR) = device
(1) = input filter
(2) = CSI binary input
plus-switching
(3) = CSO binary input
minus-switching
(4) = measured value (analogue)
(5) = measured value (binary)
Configure input
→ Chapter System configuration
Possible operating modes:
Binary input CSI (B
L
) (R
E
= 10 k
) or Namur
Binary input CSO (B
H
)
Analogue voltage measurement 0...10 V (only for input type IN FREQUENCY-B)
Pulse measurement CSI (B
L
) (frequency measurement, ratio measurement, pulse counter)
Pulse measurement CSO (B
H
) (frequency measurement, ratio measurement, pulse counter)