Programmable Serial-to-Ethernet Device Server
PDS Series User Manual, Version 2.5, Mar. 2019
-
93 -
Item
Description
Default
Slave Timeout
In
, the slave mode timeout setting is use to
set the waiting time after last character of the request sent to
the device. If the device does not respond within the timeout
value, the PDS series will return a timeout error and process
next request.
200 ms
Master ACK Timeout
(MAT)
If the PDS series does not receive any data from Slave for a
certain period, the PDS series will return an ACK character to
Master and process next request based on the configured
timeout value.
0
(Disabled)
Save current settings to
EEPROM
If the
“SET COM PORT”
button is clicked with checking “
Save current settings to
EEPROM
” option, the new settings will be saved to the PDS series only and the
new settings will be valid after the next power-on.
Apply current settings
If the “
Apply current settings
” checked when the
“SET COM PORT”
button is
clicked, the new settings will be valid immediately.
SET COM PORT
Click this button to save the revised settings to the PDS series.
Note:
After configuring COM Port Settings, please
confirm that the “Save current settings to EEPROM”
and “Apply current settings” option are checked, and
then click the “SET COM PORT” button.