#AA00dd
This function sets the multi-channel Output
Syntax:
#AA00dd[CHK](cr)
#
A delimiter character
AA
The address of the module (01 only for PDS)
00
A command used to set multi-channel output
dd
The output value
Response:
Valid Command:
>[CHK](cr)
Invalid Command:
?[CHK](cr)
Ignored Command:

*A syntax error or a communication error will result in no response.
>
A delimiter for a valid command
?
A delimiter for an invalid command
!
A delimiter for an ignore command, meaning that the module is in Host
Watchdog Timeout Mode, and the output is set to safe values
Example:
Command
Response
#01000F
>
Set the digital output of channel 3 to 0 as on. Returns success.
#010005
!
Set the digital output of channel 0 and 2 as on. Returns that the module is in Host Watchdog
Timeout Mode, and the output was been set to safe values.