Programmable Serial-to-Ethernet Device Server
PDS Series User Manual, Version 2.5, Mar. 2019
-
169 -
8.22
~AA5S
This function sets the Safe Value for the DO
Syntax:
~AA5S[CHK](cr)
~
A delimiter character
AA
The address of the module (01 only for PDS)
5S
The command used to set the safe value for the DO
Response:
Valid Command:
!AA[CHK](cr)
Invalid Command:
?AA[CHK](cr)
*A syntax error or a communication error will result in no response.
!
A delimiter for a valid command
?
A delimiter for an invalid command
AA
The address of the module (01 only for PDS)
Example:
Command
Response
@0103
>
Output the value 03. Returns success
~015S
!01
Set the current output status as the safe value. Returns success.