Programmable Serial-to-Ethernet Device Server
PDS Series User Manual, Version 2.5, Mar. 2019
-
159 -
8.13
#AA1ndd
This function sets the output of a single channel
Syntax:
#AA1ndd[CHK](cr)
#
A delimiter character
AA
The address of the module (01 only for PDS)
1n
The command used to set the output of a single channel.
n is the digital output channel number.
dd
00: sets the digital output channel to off
01: sets the digital output channel to on
Response:
Valid Command:
>[CHK](cr)
Invalid Command:
?[CHK](cr)
Ignored Command:

*A syntax error or a communication error will result in no response.
>
A delimiter for a valid command
?
A delimiter for an invalid command
!
A delimiter for an ignore command, meaning that the module is in Host
Watchdog Timeout Mode, and the output is set to safe values
Example:
Command
Response
#011201
>
Set the digital output of channel 2 to on. Returns success.
Related Topics: