Programmable Serial-to-Ethernet Device Server
PDS Series User Manual, Version 2.5, Mar. 2019
-
207 -
10.2
Modbus Message Map
The nDI and nDO parameters of each model used in the following Modbus address tables are
shown as follows:
Model name
Number of DO channels
(nDO)
Number of DI channels
(nDI)
PDS(M)-721(D), PPDS(M)-721(D)-MTCP
7
6
PDS(M)-732(D), PPDS(M)-732(D)-MTCP
4
4
PDS(M)-734(D), PPDS(M)-734(D)-MTCP
4
4
PDS(M)-743(D), PPDS(M)-743(D)-MTCP
4
4
PDS(M)-762(D), PPDS(M)-762(D)-MTCP
2
1
0xxxx: DO address (base 0)
Begin address
Points
Description
Range
Access
Type
Factory
Set Value
DEC
0~(nDO-1)
1~nDO
Digital Output Value
0 = Off
1 = On
R/W
-
HEX
0x00~0x(nDO-1)
“
R
”: Read; “
W
”: Write
1xxxx: DI address (base 1)
Begin address
Points
Description
Range
Access Type
DEC
0 ~ (nDI-1)
1~nDI
Digital Input Value
0 = Off
1 = On
R
HEX
0x00 ~ 0x(nDI-1)
“
R
”: Read