Part 1 Installation
[4] Enable operation
I/O parameter No. 24, bits 0 to 3 = 0: The RDYOUT output (system I/O) is SYSRDY (PIO trigger
program operation enabled) and the hardware is normal
(emergency stop is not actuated and no hardware errors are
detected).
I/O parameter No. 44 = 0:
The drive-source cutoff reset input is not yet used.
I/O parameter No. 47 = 3:
Output function 301 = READY output (PIO program operation
enabled and no errors of cold start level or higher have
occurred).
200-VAC control power
Normal CPU start
I/O output signal: Port No. 301
Ready output
Rdy (system I/O)
SDN (system I/O)
EMG1, EMG2 (system I/O)
ENB1, ENB2 (system I/O)
Occurrence of secret level error
Occurrence of message level error
Occurrence of operation cancellation level error
Occurrence of cold start level error
Occurrence of system shutdown level error
Enable SW = ON
Enable SW = OFF