465
Appendix
Other Parameters
No.
Parameter name
Default value
(Reference)
Input range
Unit
Remarks
12 Automatic operation
recognition type
0
0 ~ 3
0: Program is running AND all-operation-cancellation
factor is not present
1: [Program is running OR in AUTO mode] AND all-
operation-cancellation factor is not present
13~
19
(For extension)
0
20 System-memory
backup battery
installation function
type
2
0 ~ 2
0: Not installed (SEL global data/error lists cannot
be recovered from the flash ROM)
1: Not installed (SEL global data/error lists can be
recovered from the flash ROM)
2: Installed
* When the power is turned on without battery
installed, point data can be copied from the
flash ROM.
* Use of setting “1” will be prohibited for the time
being due to limitations.
* When point data is lost due to a battery error,
the point data valid before the flash ROM was
written can be restored
Input “0” (not
installed) and transfer the setting to the
controller, and then perform a software reset
without writing the flash ROM. The point data
last written to the flash ROM will be restored.
Thereafter, reset this parameter to the original
value. (No remedy is available for recovery of
SEL global data/error lists.)
21 Manual operation type
0
0 ~ 5
0: Always enable edit and SIO/PIO start (Initial
condition after connection = With safety speed)
1: Select edit and start (with password) (EU, etc.)
2: Always enable edit and SIO/PIO start (Initial
condition after connection = Without safety speed
(cancellation))
* Referenced by the PC/TP.
22 Control use region
0
0 ~ 99
0: J, 1: E, 2: EU
23 PSIZ command
function type
0
0 ~ 5
0: Maximum number of point data areas
1: Number of point data used
24 Local variable number
for storing SEL-
communication-
command return code
99
1 ~ 99,
1001 ~ 1099
25~
29
(For extension)
0
30 Option Password 00
0H
0H ~
FFFFFFFFH
HOME command option (Change prohibited)
* Change is prohibited unless instructed by the
manufacturer.
31 Option Password 01
0H
0H ~
FFFFFFFFH
Reserved (Change prohibited)
* Change is prohibited unless instructed by the
manufacturer.
32 Option Password 02
0H
0H ~
FFFFFFFFH
Reserved (Change prohibited)
* Change is prohibited unless instructed by the
manufacturer.
33~
35
(For extension)
0
0H ~
FFFFFFFFH
466
Appendix
Other Parameters
No.
Parameter name
Default value
(Reference)
Input range
Unit
Remarks
36 PC/TP data protect
setting (Program)
0H
0H ~
FFFFFFFFH
Bits 0 to 3: Protect type (0: Read/write, 1: Read
only, 2: No read/write)
Bits 4 to 7: Protect release method (0: Special
operation)
Bits 8 to 11: Protect range maximum number (1’s
place, BCD)
Bits 12 to 15: Protect range maximum number (10’s
place, BCD)
Bits 16 to 19: Protect range minimum number (1’s
place, BCD)
Bits 20 to 23: Protect range minimum number (10’s
place, BCD)
* Referenced by the PC/TP
37 PC/TP data protect
setting (Position)
0H
0H ~
FFFFFFFFH
Bits 0 to 3: Protect type (0: Read/write, 1: Read
only, 2: No read/write)
Bits 4 to 7: Protect release method (0: Special
operation)
Bits 8 to 11: Protect range maximum number (10’s
place, BCD)
Bits 12 to 15: Protect range maximum number (100’s
place, BCD)
Bits 16 to 19: Protect range maximum number
(1000’s place, BCD)
Bits 20 to 23: Protect range minimum number (10’s
place, BCD)
Bits 24 to 27: Protect range minimum number (100’s
place, BCD)
Bits 28 to 31: Protect range minimum number
(1000’s place, BCD)
* The value in the 1’s place is considered “0” for
both the protect range maximum/minimum
numbers.
* Referenced by the PC/TP
38 PC/TP data protect
setting (Symbol,
parameter)
0H
0H ~
FFFFFFFFH
Bits 0 to 3:
Protect type (Parameter) (0:
Read/write, 1: Read only, 2: No
read/write)
Bits 4 to 7:
Protect release method (Parameter)
(0: Special operation)
Bits 8 to 11: Protect type (Symbol) (0: Read/write,
1: Read only, 2: No read/write)
Bits 12 to 15: Protect release method (Symbol) (0:
Special operation)
* Referenced by the PC/TP
468
Содержание X-SEL PX
Страница 1: ...Operation ManualSeventh Edition X SEL Controller PX QX Type Tenth Edition ...
Страница 2: ......
Страница 8: ......
Страница 14: ......
Страница 39: ...15 Part 1 Installation Reference Circuit Diagram Surge absorber Solenoid valve Controller 0 V 15 ...
Страница 410: ...383 Appendix 386 ...
Страница 452: ...425 Appendix 5 428 ...
Страница 559: ......