Table 4: Installer Menu
Installer Menu
Setting Options
Menu Tasks & Explanations
SDC Wire
Connections
CR 0 REVERSE
Center Loop
0 = Reopen if center loop triggers
1 = Pause only
The default allows the barrier arm to reopen if
the Center Loop detector is triggered during
closure of the barrier arm. A setting of 1 causes
the barrier arm to only pause when triggered.
Closure begins as soon as the loop is clear
again.
Center Loop
COM or connection
to Hy5x detector
CB 0 (OFF)
CLD Disable ELD
0 = Normal operation of Free Exit
1 = Disable Free Exit
Setting 1 allows an CLD input to disable the
Free Exit Detector (ELD) until the barrier arm
is fully closed. Used in bi-directional traffic
situations.
Center Loop
COM or connection
to Hy5x detector
CP 0 (OFF)
CLD Counts PBO
0 = Immediate closure
1 = Provides addt’l open time
The default allows the Center Loop Detector
when triggered and released, to close the
barrier arm immediately. The optional setting
of 1 designates that the Smart DC Controller
remember an additional open command if the
open input is activated a second time while
the barrier arm remains open. (For example, to
prevent a vehicle from being stranded).
Center Loop
COM or connection
to Hy5x detector
EB 0 (OFF)
ELD Backoff
0 = Normal operation of Free Exit
1 = Back off close function
The default allows normal latch open operation
of the Free Exit detector. The optional setting
of 1, creates an automatic close function if a
vehicle triggers and then backs off the Free
Exit Loop detector.
Free Exit Loop
COM or connection
to Hy5x detector
RL 1 0 DISABLED
Relay 1 Logic
0 = Disabled
1 to 38 available
Configures the function of the User 1 output
relay. It has the capacity to switch both AC and
DC loads and can be used for high voltage
and/or high current loads. Connect devices
directly to the top of the relay: COM and either
NO and/or NC contacts.
Multiple logic function options exist. See
User
Relays - Programming Procedure on page
39.
COM
User 1 Relay
RL 2 0 CLOSE LIMI
Relay 2 Logic
0 = Disabled
Relay 2 configures the function of the User 2
output relay, which is an electronic relay with
the capacity for switching a DC load only.
NOTE:
In the StrongArmPark DC, it is
recommended to use the User 2 Relay for
connection to the LED arm lighting.
COM
User 2 Relay
RL 3 0 DISABLED
thru
RL 10 0 DISABLED
Relay Logic
0 = Disabled
1 to 38 available
Similar to Relay 1 Logic.
COM
User 3 through 10
Relay
TL 2 (45 SECS)
Open Time Alert
2 = 45 second delay
0 = 0s delay
1 = 15s
3 = 75s
4 = 105s
5 = 135s
This menu item only appears if the #8 User
Relay function has been selected. It adjusts the
time delay before activation of the User Relay
function.
User Relay
28
MX3650-01 Rev. D
StrongArmPark DC Programming & Operations