UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
4 Control Panel
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
68
The configured number of batteries must match the actual number. When the actual number
changes, change the configured number. If the configured number is less than the actual
number, the battery lifespan is shortened. If the configured number is greater than the actual
number, battery leakage may cause a fire.
The UPS2000-G-6 kVA/10 kVA parallel system cannot shares a battery string.
If a UPS2000-G-15 kVA/20 kVA parallel system shares a battery string, set the same
battery string capacity and charge current for each UPS.
Battery capacity (Ah) = Capacity of a single battery string x Number of parallel battery
strings/Number of parallel UPSs sharing a battery string. Maximum charge current (Ah) =
0.1 x Capacity of a single battery string x Number of parallel battery strings/Number of
parallel UPSs sharing a battery string. If the calculated maximum charge current is greater
than 4 A, set it 4 A. Use two UPSs sharing a 65 Ah battery string as an example: If the
calculated battery capacity is 65 x 1/2 = 32.5, set it to 32 Ah; if the calculated maximum
current is 0.1 x 65 x 1/2 = 3.25, set it to 3.0 A.
If a single 15 kVA/20 kVA UPS connects to two battery packs, the maximum charge
current must be less than or equal to 2.0 A.
Basic
screen
Figure 4-37
Basic screen
−
Batteries
/
Positive battries
/
Negative battries
parameters
Set the number of batteries. The value ranges from 16 to 20. The default value is 20.
When the number of batteries
N
is less than 20, the system output power is derated
to
N
/20 in battery mode. The parameter is configurable in non-battery mode or
non-battery ECO mode. You need to set Number of batteries on the UPS2000-G-3
kVA/6 kVA/10 kVA, and set two battery strings (positive and negative) on the
UPS2000-G-15 kVA/20 kVA.
−
Battery capacity
parameter
Set the battery string capacity. The value ranges from 7 Ah to 1000 Ah. For the
UPS2000-G-3 kVA/6 kVA, the default value is 7 Ah on a standard model and 40 Ah
on a long backup time model; for the UPS2000-G-10 kVA, the default value is 9 Ah
on a standard model and 65 Ah on a long backup time model; for the
UPS2000-G-15 kVA/20 kVA, the default value is 65 Ah on a long backup time
model. Battery capacity is the sum of all battery capacities, set the parameters based
on the actual battery capacity. The parameter is configurable in non-battery mode or
non-battery ECO mode.
−
Intelli. Hibernation
parameter