UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
2 Quick Introduction
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
22
Component Model
Function
Remarks
transformer
box
equipment. Compared
with the output
transformer on an
industrial frequency
UPS, the output
transformer box
provides isolation
functions even in
bypass mode. The
isolation transformer is
a 2:1:1
industrial-frequency
transformer. It converts
one 220 V output
voltage into two
isolated 110 V outputs.
transformer box
is 6 kVA,
single-phase. It
is used for the
UPS2000-G-6
kVA.
10 kVA
output
isolation
transformer
box
DGL-10/0.22
The output
isolation
transformer box
is 10 kVA,
single-phase. It
is used for the
UPS2000-G-10
kVA.
Standard
battery pack
(7 Ah, 20
batteries)
ESS-240V12-7AhBPVBA0
1
ESS-240V12-7AhBPVBA0
2
Each battery pack
consists of twenty 12
V, 7 Ah VRLA
batteries connected in
series. It is a standard
configuration for the
UPS2000-G-6 kVA. A
maximum of four
battery packs are
connected in parallel.
The
UPS2000-G-15
kVA/20 kVA
uses at least two
battery packs.
Standard
battery pack
(9 Ah, 20
batteries)
ESS-240V12-9AhBPVBA0
1
ESS-240V12-9AhBPVBA0
2
Each battery pack
consists of twenty 12
V, 9 Ah VRLA
batteries connected in
series. It is a standard
configuration for the
UPS2000-G-10 kVA.
A maximum of four
battery packs are
connected in parallel.
Modbus card
RMS-MODBUS01A
Provides two cascaded
RJ45 ports to
implement networking
over the Modbus or
YDN-23 protocol.
N/A
Dry contact
card
RMS-RELAY01A
Provides six alarm dry
contact outputs (normal
mode, battery mode,
bypass mode, low
battery voltage, bypass
backfeed, and UPS
faults) and two dry
contract control inputs
(one is the shutdown
N/A