UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
3 Installation
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
39
Model
Single-phase/three-phase
Two live wires
Rated Voltage
and Current
Recommended
Contactor
Models
(Schneider
contactors)
Rated
Voltage and
Current
Recommend
ed Contactor
Models
(ABB
contactors)
V2
A
A
70
UPS2000-
G-10KRTL
-V2
220 V AC, 230 V
AC, 240 V AC, 65
A
LC1-D50A for
single-phase
input
LC1-DT60A for
three-phase
input
208 V AC,
220 V AC, 65
A
AF50-30-11*
70
UPS2000-
G-15KRTL
(three-phas
e input)
220 V AC, 230 V
AC, 240 V AC, 32
A
LC1-DT60A for
three-phase input
N/A
N/A
UPS2000-
G-20KRTL
(three-phas
e input)
220 V AC, 230 V
AC, 240 V AC, 40
A
N/A
N/A
UPS2000-
G-15KRTL
(single-pha
se input)
UPS2000-
G-20KRTL
(single-pha
se input)
220 V AC, 230 V
AC, 240 V AC,
125 A
LC1-D80 for
single-phase input
208 V AC,
220 V AC,
125 A
AF110-30-11
*70
Table 3-4
Control relay parameters
Recommended Model
Parameters
HF18FF/012 (HONGFA control relay)
Dry contact: NC
Breaking capability: 250 V AC, 5 A
Coil: 12 V rated voltage; rated current of
less than 1 A
MY2N-J DC12V (OMRON control relay)
HJ2-L-DC12V (Panasonic control relay)
3.3.1 Feedback Prevention Connections (With Dry Contract
Control)
connections (with dry contract control).