UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
2 Quick Introduction
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
18
For UPS2000-G-3 kVA, UPS2000-G-6 kVA and UPS2000-G-10 kVA, if the UPS input
uses two live wires (208 V/220 V system), all L and N wires change to L1 and L2 wires. If
the AC input of the UPS2000-G-10 kVA uses two live wires, connect AC INPUT L1, L2,
and L3 that are short-circuited with a short-circuit busbar to live wire L1, and connect AC
INPUT N to live wire L2.
If the AC input of the UPS2000-G-15 kVA/20 kVA uses two live wires, connect bypass
and mains input bL1, bL2, bL3, mL1, mL2, and mL3 that are short-circuited with a
short-circuit busbar to live wire L1, and connect the input N and N with a short-circuit
busbar to live wire L2.
In addition, if the AC input and AC output uses two live wires, the input and output ends
must connect to two-pole circuit breakers, that provided by the user.
shows the front and rear views of the UPS2000-G-3 kVA/6 kVA.
the front and rear views of the UPS2000-G-10 kVA.
shows the front and rear views
of the UPS2000-G-15 kVA/20 kVA.
Figure 2-3
Front and rear views of the UPS2000-G-3 kVA/6 kVA
(1) Control panel
(2) AC input port
(3) AC output
ports (pL and sL)
(4) Output
sockets
(5) Parallel ports
(6) Control area network
(CAN) communications
ports (MON1 and MON2)
(7) Optional card
slot
(8) Battery
temperature
sensor port
(9) USB port
a
(10) Emergency power-off
(11) Maintenance (12) Fuse base