UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
132
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
0044-01
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: An error
occurred during software
loading.
Measure: Contact the
manufacturer to load
software.
0044-02
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: Software and
hardware versions do not
match.
Measure: Contact the
manufacturer to load
software.
0044-03
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: Software and
hardware versions do not
match.
Measure: Contact the
manufacturer to load
software.
0044-04
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: An error
occurred during software
loading.
Measure: Contact the
manufacturer to load
software.
0044-05
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: Software and
hardware versions do not
match.
Measure: Contact the
manufacturer to load
software.
0044-06
Incompatible
ver.
Critical Manual
clear/Power-off
clear
The UPS startup
is not allowed.
Possible cause: Software and
hardware versions do not
match.
Measure: Contact the
manufacturer to load
software.
0045-03
Charger
alarm
Critical Manual
clear/Power-off
clear
The charger in
the UPS stops.
Possible cause: The charger
capacitor is faulty.
Measure: Contact Huawei
technical support for repair.
0045-04
Charger
alarm
Critical
Possible cause: The charger
output is short-circuited.