UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
139
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
start inverters.
perform parallel parameter
synchronization.
NOTE
After you perform parallel
parameter synchronization,
contact Huawei technical
support if some parallel
parameters are still
inconsistent.
0131-01
Ambient
overtemperat
ure
Minor
Automatic clear
An alarm is
generated.
Possible causes:
The ambient temperature
in the UPS equipment
room exceeds the alarm
threshold (default value:
40°C).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature
and humidity transducer.
0133-01
Ambient
undertempera
ture
Minor
Possible causes:
The ambient temperature
in the UPS equipment
room is below the alarm
threshold (default value:
0º
C).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature
and humidity transducer.
0134-01
Ambient
overhumidity
Minor
Possible causes:
The ambient humidity in
the UPS equipment room
exceeds the alarm
threshold (default value: