C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
138
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
Measure: Restart the UPS
after the alarm is cleared.
0094-01
Redundancy
failure
Minor
Automatic clear
N/A
Possible causes:
The configured number
of redundant UPSs
exceeds the maximum
allowed value.
The load exceeds the
rated loading capacity of
the requisite UPSs in the
parallel system.
Measures:
Reduce the number of
redundant UPSs or set the
system to be
non-redundant.
Reduce the load or
replace the UPS with a
larger-capacity UPS.
0096-01
Abnormal
ECO volt.
Minor
Automatic clear
Transfer to
bypass mode is
prohibited. If the
bypass is
supplying power,
the UPS transfers
to another
working mode.
Possible cause: The ECO
input is abnormal.
Measure: Check whether the
ECO input voltage or
frequency exceeds the
configured range. If yes,
change the range or wait
until the bypass input
recovers.
0105-05
Comm.
failed.
Minor
Automatic clear
The monitoring
module cannot
monitor the
digital signal
processor (DSP)
of the power
module.
Possible causes:
The communications
cable is faulty.
An internal fault occurs
in the UPS.
Measures:
Check the
communications cable.
Contact Huawei technical
support for repair.
0125-01
Incon. paral.
param.
Critical Automatic clear
An alarm is
generated, and
all the UPSs in
the parallel
system cannot
Possible cause: The parallel
parameters are not set
consistently on the UPSs.
Measure: Set the parallel
parameters consistently, or