UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
121
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
down.
The UPS may
transfer to
another
working
mode or shut
down.
0005-01
Mains neutral
loss
Minor
Automatic clear
The UPS
transfers to
battery mode.
If no battery
is equipped,
the UPS shuts
down.
The UPS
changes the
working
mode or shuts
down.
Possible cause: The mains
input neutral wire is not
connected.
Measure: Check that mains
input power cables are
correctly connected.
0007-01
Batt. trans.
overlimit
Minor
Manual
clear/Power-off
clear/Automatic
clear
The UPS does
not transfer back
to normal mode
even when the
mains is normal.
Possible cause: The mains
voltage fluctuates frequently.
The UPS has transferred
from normal mode to battery
mode within 2 minutes for
10 consecutive times. The
rectifier locks out in battery
mode.
Measure: Check the mains.
0008-01
Rect. start
overlimit
Minor
Manual
clear/Power-off
clear
The UPS cannot
start.
Possible cause: The mains
voltage frequently becomes
abnormal during startup.
Measure: Check the mains
input voltage. If the voltage
becomes normal, clear the
alarm and restart the UPS.
0010-01
Abnormal
BPS volt.
Minor
Automatic clear
The UPS cannot
transfer to bypass
mode. If the
bypass is
supplying power,
the UPS changes
the working
mode.
Possible causes:
The bypass input voltage
is abnormal.
The bypass input
frequency is abnormal.
Measures:
Check whether the bypass
input voltage exceeds the
configured range. If yes,
0010-02
Abnormal
BPS volt.
Minor