UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
9 Technical Specifications
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
100
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
125% ≤ load < 150%: 1 minute in bypass mode
Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.
Input mode
One mains input
One mains input
Two mains inputs
The upper and lower thresholds are configurable on the LCD.
9.5 Output Electrical Specifications
Table 9-5
Output electrical specifications
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Rated capacity
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Output PF
0.9
Rated output
voltage
208 V AC, 220 V AC, 230 V AC, or 240
V AC (single-phase output; select a
voltage system by setting a voltage level
on the LCD.)
208 V AC, 220 V AC,
230 V AC, or 240 V AC
(single-phase output;
select a voltage system by
setting a voltage level on
the LCD.)
380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the
LCD.)
Output voltage
tolerance
±1%
Total harmonic
distortion of
output voltage
(THDv)
< 4% (non-linear load)
< 2% (resistive load)
Crest factor
A maximum of 3:1
Inverter
overload
capability
105% ≤ load < 125%: transfer to bypass mode after 5 minutes
125% ≤ load < 150%: transfer to bypass mode after 1 minute
Load ≥ 150%: transfer to bypass mode after 0.1 second
The UPS stops supplying power if the bypass is abnormal.