UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
B LCD Menus and Parameters
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
118
Main
Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Value Range
Preset Value
(configurable
after the
inverter shuts
down)
Control
Startup
N/A
N/A
N/A
N/A
Shutdown
Replace
Batteries
Maintain
Batteries
Shallow
Discharge Test
Capacity Test
Stop Test
Manual
Equalized
Charging/Manu
al EC for Pos.
/ManualEC for
Pos.
Manual Float
Charging/Manu
al FC for Neg.
/Manual FC for
Neg.
Sync Paral.
Param.
N/A
Reset Password
About
Model
N/A
N/A
N/A
N/A
ESN
Version
The bypass frequency range is associated with the ECO frequency range (the bypass frequency
range is ±0.5 Hz, ±1 Hz, ±2 Hz, ±3 Hz, ±4 Hz, ±5 Hz, or ±6 Hz; the ECO frequency range is ±0.5
Hz, ±1 Hz, ±2 Hz, or ±3 Hz).
The bypass frequency range must be greater than or equal to the current ECO frequency range (if the
ECO frequency range is ±3 Hz, the bypass frequency range is ±3 Hz, ±4 Hz, ±5 Hz, or ±6 Hz).
The ECO frequency range must be less than or equal to the current bypass frequency range (if the
bypass frequency range is ±1 Hz, the ECO frequency range is ±0.5 Hz or ±1 Hz).
The voltage level is associated with the upper threshold for bypass voltages (10%, 15%, 20%, 25%,
or 30%).