UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
C Alarm Handling
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
140
Alarm ID
(Alarm
ID-Alarm
Cause)
Alarm
Name
Alarm
Level
Alarm Clear
Mode
Impact on the
System
Repair Proposal
90%).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
and humidity transducer.
0135-01
Ambient
underhumidit
y
Minor
Possible causes:
The ambient humidity in
the UPS equipment room
is below the alarm
threshold (default value:
10%).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
and humidity transducer.
0136-01
Faulty
temperature
and humidity
module
Minor
Possible causes: The
temperature and humidity
module is faulty.
Measures:
Check parameter settings
of the temperature and
humidity transducer.
Replace the temperature
and humidity transducer.
0158-01
On bypass
Minor
Automatic clear
If the bypass is
abnormal, the
UPS may power
off.
Possible causes:
The inverter is not
started.
The load exceeds the
rated inverter loading
capacity.
The inverter is faulty.
Measures: