UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
E Battery Shallow Discharge Test
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
144
E
Battery Shallow Discharge Test
Context
A shallow discharge test method that tests the battery loop reliability and short-time backup
capacity after batteries are charged for a long time (60 days by default, 30 days to 90 days
configurable).
Procedure
Step 1
Check the battery status for test start conditions.
1.
On the
Main Menu
screen, choose
Status
and click
. On the
Status
screen, locate
Battery Status
.
Figure E-1
Battery Status menu
Status
: The battery status is
NA
(battery not connected or reversely connected),
Equalized
charging
,
Float charging
,
Hibernating
, or
Discharging
.
Capacity
: indicates the remaining battery capacity.
Backup time
: indicates the estimated discharge duration. The value is
NA
during battery charging.
2.
Batteries in
Hibernating
state cannot start a shallow discharge test. Choose
Control
and
Maintain Batteries
, and then click
Manual Float Charging
to switch the batteries to
the float charging state. If the batteries hibernate due to a charger alarm, the batteries can
switch between float charging and equalized charging only after the alarm is cleared.