15.7 Rules for Deploying T/H Sensors
Context
Determine the number of T/H sensors to be deployed based on the number of air
conditioners.
Each air conditioner can be configured with three more external T/H sensors.
Procedure
Step 1
Mark management areas based on the air conditioner layout.
Scenario 1: There is an odd number of IT cabinets between air conditioners. In this
scenario, categorize the cabinet in the middle of the two air conditioners to the area of
the air conditioner on the left (front view), as shown in
Components in the background with the same color belong to the same area.
Figure 15-72
Categorizing an odd number of cabinets
Scenario 2: There is an even number of IT cabinets between air conditioners. In this
scenario, categorize the cabinets evenly, as shown in
Components in the background with the same color belong to the same area.
Figure 15-73
Categorizing an even number of cabinets
Step 2
Assign T/H sensors by area.
Assign three T/H sensors to each area as follows:
1.
Assign the first T/H sensor to the cabinet furthest from the air conditioner, as shown by
(1) in