Link the alarm beacon and ATS. When the alarm beacon is triggered, the ATS
disconnects non-firefighting power supply.
This section describes how to link a JB-QBL-QM200 gas extinguishing controller and the
ATS using cables.
Preparations
Tool: Phillips screwdriver
Material: cable tie
Procedure
Connect linkage cables between the drive output ports for the fire alarm bell on the gas
extinguishing controller and the non-firefighting power disconnection ports on the ATS,
as shown in
Figure A-10
Connecting linkage cables between the fire alarm bell and ATS
Connect linkage cables between the drive output ports for the alarm beacon on the gas
extinguishing controller and the non-firefighting power disconnection ports on the ATS,
as shown in