FusionModule2000 Smart Modular Data Center
Installation Guide
17 Connecting Cables
Issue 02 (2018-03-31)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
274
Figure 17-9
Routing power cables and signal cables
(1) Network cabinet
(2) Optical fiber
(3) Signal cable
(4) Smart ETH gateway
(5) PDC
(6) Power cable
17.4 Cable Routes for the Single-Row Aisle Containment
Scenario (Power Supply and Distribution Cabinet)
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.