17 Connecting Cables
Issue 02 (2018-03-31)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
273
To avoid damaging the cable sheathings, do not press or stab cables with a hard object and do
not drag cables on the ground at will during cable layout.
3.
Attach labels to both ends of cables that you have laid out.
Ensure that the labels are clear, endurable, and consistent between both ends.
Step 3
Label cables.
1.
(Optional) Prepare labels based on site requirements.
Label information must be clear and specific.
Labels must be easy to attach and can be securely attached.
Labels must be resistant to corrosion and deterioration.
2.
Remove the simple labels attached to a cable during layout and attach labels to both ends
of the cable.
Labels must be securely attached.
Labels must be attached in eye-catching positions on cables for ease of maintenance.
The labels on both ends of a cable must be the same.
----End
17.3 Cable Routes for the Dual-Row Aisle Containment
Scenario (Power Supply and Distribution Cabinet)
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.