FusionModule2000 Smart Modular Data Center
Installation Guide
15 Installing Monitoring Devices
Issue 02 (2018-03-31)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
208
3.
No gap exists between the revolving door magnetic lock and the magnet.
If any of the preceding conditions is not met, the magnetic lock fails to attract the magnet.
Troubleshoot the magnet as follows:
1.
Check the circuit and rectify any circuit fault.
2.
Adjust the magnet base and the door panel to align the magnetic lock with the magnet
face-to-face. Ensure that the deviation is minimum.
3.
If a gap exists between the revolving door magnetic lock and the magnet, rectify the fault
as shown by (1) in
4.
If the magnet is not level, rectify the fault as shown by (2) in
magnet levelness.
Figure 15-44
Adjusting the gap
----End
15.4.7 (Optional) Installing a Sliding Door Magnetic Lock
Context
A sliding door magnetic lock is optional in dual-row cabinet scenarios.
The BOM number for a sliding door magnetic lock is 02070215. The following components
are required for installing a magnetic lock.